Contents
- Which Restaurant Devices Should Be on the UPS?
- Which Devices Should Not Be on the UPS?
- Which Type of UPS Is Suitable?
- What Size UPS? A Worked Example
- Battery Runtime: Until Service Ends?
- Installing a UPS Near a Kitchen
- The Era of Online Ordering and Delivery
- Restaurants in Areas With Frequent Outages
- Display Fridges in Cafés and Patisseries
- Frequently Asked Questions
A power cut during a busy lunch or dinner service is one of a restaurant’s worst scenarios. The ordering system shuts down, orders on their way to the kitchen are lost, the POS cannot take payments, delivery orders stop arriving and diners cannot pay their bills. Even if the power returns after a few seconds, restarting systems and recovering orders disrupts service for a long time.
In this article we share which devices need protecting when choosing an uninterruptible power supply (UPS) for restaurants, cafés, patisseries and fast-food outlets, along with a worked sizing example.
Which Restaurant Devices Should Be on the UPS?
| Device | Why it matters |
|---|---|
| POS and ordering terminals | Orders and payments |
| Order server / main PC | Protecting open tables and bills |
| Kitchen printers and order screens | Getting orders to the kitchen |
| Modem, switch, Wi-Fi | Card payments, online orders, guest internet |
| Camera recorder | Security and continuous recording |
| Cash register / e-receipt printer | Issuing receipts and invoices |
Which Devices Should Not Be on the UPS?
Espresso machines, ovens, grills, fryers, water heaters and air conditioners are high-power heating loads. Connecting them to a UPS requires a very large UPS and cuts battery runtime to minutes. If kitchen equipment must keep running, the right solution is a generator. The UPS protects the business’s ordering and payment backbone. For using a UPS and generator together, see UPS and generator compatibility.
Which Type of UPS Is Suitable?
- Small cafés and single-till businesses: A 1–1.5 kVA line-interactive UPS may be enough to protect the till, modem and printer.
- Medium and large restaurants: With several POS terminals, kitchen screens and a server, a central online UPS is the better choice. An online UPS has no transfer time, so systems are unaffected even when the mains fluctuates.
- Chains: Using the same UPS model in every branch simplifies maintenance and battery replacement.
What Size UPS? A Worked Example
| Load | Estimated power |
|---|---|
| 2 POS / ordering terminals (2 × 120 W) | 240 W |
| Order PC | 250 W |
| 2 kitchen printers and order screen | 140 W |
| Modem, switch, Wi-Fi | 60 W |
| Camera recorder and cameras | 140 W |
| Total | 830 W |
830 W ÷ 0.9 ≈ 920 VA; with a 25% safety margin ≈ 1.2 kVA. A 1.5–2 kVA line-interactive or online UPS suits this restaurant. We explain the general method in what size UPS should I buy.
Battery Runtime: Until Service Ends?
In restaurants the aim is usually to be able to close open bills and keep short outages unnoticed by customers. For this, 15–30 minutes of battery time is enough for most businesses. Businesses without a generator in areas with long outages can extend this by adding external batteries to the UPS.
Installing a UPS Near a Kitchen
Kitchens are hot, humid and greasy, conditions that wear out UPS fans and batteries. The UPS should be located away from the kitchen in a cool, dry place, such as a cupboard behind the counter or the storeroom. An annual check and clean extends UPS life. Our technical service team carries out battery tests and maintenance on site. To learn when batteries should be replaced, see when should UPS batteries be replaced.
The Era of Online Ordering and Delivery
Food delivery platforms make up a significant share of restaurant revenue. These orders arrive via the internet connection and order tablets or PCs. If the modem shuts down during an outage, the business may appear “closed” on the platform, and incoming orders cannot be accepted and are cancelled. This is not only a lost sale at that moment; frequent cancellations can also hurt ranking on the platform and customer satisfaction. Even a small UPS supplying the modem, router and order devices largely removes this risk.
Restaurants in Areas With Frequent Outages
In summer, the grid in tourist areas and busy commercial streets comes under strain; short outages and voltage dips become more frequent. Recommendations for restaurants in these areas:
- Protect till and ordering systems with an online UPS; short outages and fluctuations go completely unnoticed.
- If voltage is constantly low, consider a voltage regulator at the site entry for fridges and compressor equipment.
- If long outages are frequent, combine a generator for the kitchen and refrigeration with a UPS for till systems.
Display Fridges in Cafés and Patisseries
Display fridges in patisseries and cafés stay cold for a short time during an outage. To prevent product loss in long outages, a generator is needed. However, if the display fridge’s digital thermostat or control board fails during frequent outages, a small UPS supplying only the control circuit, or a site-wide voltage regulation solution, can be considered. You can share the technical details of your equipment with us to determine the right solution.
Frequently Asked Questions
Can I connect the espresso machine to the UPS?
It is not recommended. Espresso machines use heaters of several kilowatts, which makes the UPS very large and cuts battery runtime to minutes.
Are delivery orders lost during an outage?
If the modem and order PC are on the UPS, online orders keep arriving during the outage.
Should I put a separate UPS on each till?
For businesses with 1–2 tills, a UPS per till can be practical. With more devices, a single central UPS makes monitoring and battery maintenance easier.
When should I plan the UPS for a new restaurant?
Before the electrical installation is done. If sockets for tills, ordering and network devices are designed to be fed from a separate UPS circuit, no changes are needed later.
Do we have to close when the UPS batteries are replaced?
On most models battery replacement is quick and can be scheduled outside opening hours. On some UPS units batteries can even be replaced while the unit is running.
A UPS recommendation for your business
Tell us about your POS, ordering and kitchen systems; we will calculate the right line-interactive or online UPS capacity for your business. You can call us on 0212 210 75 51 or send an email to elsi@elsi.com.tr.