Protecting reception, the property management system, key cards, Wi-Fi and security systems against outages

UPS Selection for Hotels: Reception and Wi-Fi

How do you choose a UPS for hotels and guesthouses? What size is needed for the property management system, key-card system, Wi-Fi, telephone exchange and cameras, and when is a rack-type or modular UPS preferred? A worked example.

  • ELSIPOWER technical team
  • Nov 23
  • 5 min read
UPS Selection for Hotels: Reception and Wi-Fi
Contents
  1. Which Hotel Systems Should Be on the UPS?
  2. Rack-Type UPS for the System Room
  3. Central and Modular Solutions for Large Hotels
  4. What Size UPS? A Worked Example (Medium-Sized Hotel)
  5. Battery Runtime and Generator Compatibility
  6. Pre-Season Checks
  7. Guest Experience and Online Reviews
  8. Restaurants, Spa and Meeting Rooms
  9. A Simple Solution for Boutique Hotels and Guesthouses
  10. Frequently Asked Questions

A hotel guest’s experience depends largely on invisible systems: the property management system (PMS) used for reservations and check-in, the key-card system, Wi-Fi, the telephone exchange, payment systems and security cameras. If these shut down during a power cut or a short fluctuation, the result is queues at reception, guests unable to get into their rooms, no internet and negative reviews.

In this article we share which systems need protecting when choosing an uninterruptible power supply (UPS) for hotels, boutique hotels and guesthouses, the types of UPS and a worked sizing example.

Which Hotel Systems Should Be on the UPS?

SystemEffect of an outage
Property management system (PMS) serverReservations, check-in/out and billing stop
Reception PCs and printersGuest transactions cannot be processed
Key-card encoderNew key cards cannot be issued
Wi-Fi, switches, internet lineGuests lose connectivity
Telephone exchangeRoom and outside calls are cut off
Camera recorder and alarmSecurity recording stops
Restaurant and bar POSPayments cannot be taken

Lifts use a separate lift rescue UPS that brings the car to the nearest floor and opens the doors during an outage. Kitchen equipment, air conditioning and pool pumps are backed up by the generator instead of the UPS.

Rack-Type UPS for the System Room

In hotels, the PMS server, switches, telephone exchange and recorder are usually gathered in a system cabinet. A rack-type online UPS that mounts directly in these cabinets saves space and keeps cabling tidy. With a network monitoring card, UPS status, battery level and alarms can be tracked remotely, and servers can be shut down safely if an outage goes on.

Central and Modular Solutions for Large Hotels

In hotels with hundreds of rooms and in resorts, critical loads are spread across floors and blocks. In that case:

  • Central supply can be provided by a three-phase online UPS of 10–20 kVA or more.
  • For growing needs and redundancy, a modular UPS can be chosen: capacity grows by adding modules, and the system keeps running even if one module fails.

What Size UPS? A Worked Example (Medium-Sized Hotel)

LoadEstimated power
PMS server500 W
3 reception PCs and printer600 W
Switches, router, Wi-Fi controller400 W
Telephone exchange200 W
Camera recorder and cameras400 W
Key-card encoder and other160 W
2 POS and order printer300 W
Total2,560 W

2,560 W ÷ 0.9 ≈ 2.85 kVA; with a 25% safety margin ≈ 3.6 kVA. A 6 kVA online UPS is a suitable choice for this hotel. If the Wi-Fi access points on each floor are powered by PoE switches, those switches must also be on the UPS.

Battery Runtime and Generator Compatibility

In hotels with a generator, the UPS keeps systems running until the generator takes over. In boutique hotels and guesthouses without a generator, the aim may be for Wi-Fi, reception and security systems to run for at least an hour, for which an external battery cabinet is added. We explain how to calculate runtime in how long a UPS runs.

Pre-Season Checks

In seasonal hotels, UPS units may sit lightly loaded or switched off for months. A battery test and general check before the season opens means no surprises during the busy period. Our technical service team carries out checks and battery renewal on site.

Guest Experience and Online Reviews

A short outage at a hotel may seem a minor technical event. For the guest, however, it means waiting at check-in, being unable to get online in the evening or being unable to enter the room. These experiences often show up in online reviews and affect the hotel’s rating. A properly planned UPS infrastructure means guests never notice the outage: Wi-Fi keeps working, reception carries on and key cards can be issued.

Restaurants, Spa and Meeting Rooms

Other parts of the hotel also have systems that need protecting:

  • Restaurants and bars: POS, ordering and kitchen printers. Kitchen equipment is supplied by the generator.
  • Meeting and event rooms: Sound systems, projection and simultaneous interpretation equipment. An outage during an event directly affects the organisation.
  • Spa and fitness areas: Booking and control panels. Pool pumps and heaters are kept off the UPS.
  • Technical centre: Building management system (BMS), fire and gas detection panels and emergency announcement system.

These loads can be supplied from a single central UPS or from zone UPS units, depending on the building’s size and electrical distribution.

A Simple Solution for Boutique Hotels and Guesthouses

Small businesses do not need a complex set-up. A 2–3 kVA online UPS supplying the reception PC, modem, Wi-Fi access points and camera recorder, with external batteries added if needed, meets the needs of most boutique hotels. If outages are frequent in the area, it can be planned to work together with a generator.

Frequently Asked Questions

Should we put a separate UPS on each floor?

If floor switches are spread out, a small rack UPS can go in each floor cabinet, but supplying them from a central UPS makes monitoring and battery maintenance easier. The decision depends on the building’s cabling.

Do key-card door locks open when the power fails?

Room locks usually run on their own batteries; the part affected by an outage is the encoder that issues new cards and the reception system. The encoder should therefore be on the UPS.

Can we monitor the UPS remotely?

Yes. UPS units with a network monitoring card let you track battery level, load and alarms from a computer and receive email alerts during an outage.

Does installing a UPS disrupt hotel operations?

Installation usually requires a short power interruption and is planned for the quietest hours. Existing systems can be supplied via bypass to minimise downtime.

Should we switch the UPS off out of season?

Batteries in a UPS that is switched off for a long time can self-discharge and be damaged. Leaving the UPS on, or charging it at intervals, is better for battery life.

UPS planning for your hotel

Tell us your number of rooms and the equipment in your system room; together we will choose the right option from rack-type, three-phase or modular UPS solutions. You can call us on 0212 210 75 51 or send an email to elsi@elsi.com.tr.

ELSIPOWER technical teamElsi Güç Sistemleri — UPS, voltage regulator and battery solutions.
Share: WhatsApp LinkedIn Facebook X

Let’s choose the right solution together

Call us or send a WhatsApp message — our engineers will size the right ELSIPOWER product for your load and send you a quotation.

  • 7/24 · Technical service support
Contact us with Whatsapp